Introduction
When it comes to operating a generator, understanding the control panel is crucial for efficient and safe use. In this blog post, we'll guide you through the basic navigation of the FG Wilson DCP-10 Digital Control Panel, an essential component of FG Wilson generators. Accompanied by a helpful video tutorial, this guide will ensure you're well-equipped to manage your FG Wilson generator effectively.
Powering Up and Initial Display
When you first power up your FG Wilson generator, the DCP-10 panel will undergo a self-test. Once it displays "Ready," you'll know it's time to navigate the menus and view the parameters. The display might dim after a few seconds for energy conservation, but don't worry; it's just a battery-saving feature.
Key Buttons and Their Functions
-
Right Arrow Button:
- Use this to scroll through the submenus.
- It also allows you to modify and confirm changes in the menus.
-
Silence Alarm Button:
- In case of an audible alarm, this button lets you silence it.
-
Auto and Manual Mode Buttons:
- The LED indicator shows the current mode.
- To switch to auto mode (allowing automatic transfer and start by the transfer switch), hold the auto button for 2 seconds.
- To return to manual mode, press and hold the manual button for the same duration.
-
Red and Green Buttons (with Plus and Minus):
- These are used for starting (green) and shutting down (red) in manual mode.
- They also help increase or decrease parameter values in submenus.
-
Alarm Indicator and LED:
- The LED flashes for pre-alarms or warnings and stays solid for alarms or shutdowns.
Simulating a Start Sequence
To give you a practical understanding, the video tutorial includes a simulated start sequence. You'll notice how the generator goes through a three-start sequence, eventually leading to a start failure alarm for demonstration purposes. This shows how the panel indicates attempts and alarms, and how to reset alarms using the red stop button.
Monitoring Critical Parameters
Once the engine starts, or during its start attempts, you can scroll through various screens displaying critical parameters like:
- Hertz
- RPM
- Engine hours
- Oil pressure
- Temperature
- Battery voltage
- Line to neutral voltage (set up as a single-phase unit in the demonstration)
- Amperage on line one and line two
These readings are vital for monitoring the health and performance of your generator.